3. Safety Distances
Within a radius of 100 cm in front of and 40 cm
aroundthestove,ammable,combustible,orheat-
sensitive materials (e.g. furniture, wood or plastic
panelling, curtains, etc.) are not allowed to be loca-
tedintheheatradiatingareaofthereboxwindow
(g.1).
Behind the stove, outside the area of radiation, a
distance of 15 cm or 12 cm (when situated in a cor-
ner)mustbemaintainedtoanyammablematerials
(g.1).
WARNING!
Flammable ooring materials (e.g. wood,
laminate, carpeting etc.) must be protected
with a oorplate made of non-combustible
material (e.g. tiles, safety glass, slate, or
sheet steel).
The size of the oorplate must be lar-
ger than the base of the stove by at least
60 cm in front and at least 22 cm at the
sides of the stove (g. 2).
4. Connection of Multiple Devices in
Direct Vent Operation
WhentheLunoB.13isoperatedasadirectventmo-
del, more than one device can be connected to the
chimney under the following conditions:
CAUTION!
All connected replace stoves must be in
the same building unit or in the same ef-
fective area of the ventilation system.
The inlets for the combustion air ducts are
located in areas of equal pressure (same
pressure ratios), wind-induced pressure
uctuations have to be avoided.
The inlets for the combustion air ducts are
located in areas of equal pressure (same
pressure ratios), wind-induced pressure
uctuations have to be avoided.
Dimensions in cm
Dimensions in cm
15
40
100
12
12
100
g. 2
22
60
22
g. 1
R
a
d
i
a
t
i
n
g
A
r
e
a
R
a
d
i
a
t
i
n
g
A
r
e
a
oorplate